Domestic Water Storage Tank
•The ParkUSA® BreakTank® is a packaged
water storage system complete with tank,
controls, and fill valves. A BreakTank is a
necessary component in multilevel buildings
to provide adequate water needs
for Fire, Domestic, & Irrigation applications.
ParkUSA has fabricated BreakTanks for more
than 25 years in accordance with the
American Welding Society Specifications,
AISC, NFPA, and the Uniform Building Code.
The fabrication of reliable and durable
products requires knowledge, experience
and investment. The Engineering team at
ParkUSA designs break-tanks that are
fabricated for project specifications and size
requirements to meet all individual needs.
Complete fabrication is performed at our
Houston plant with certified material and
personnel. Factory coating and abrasive
blasting are performed in our new High-
Tech blast/paint facility, offering excellent
corrosion and abrasion resistance.
Features
Dolor Sit Amet
- Structurally & hydraulically engineered
- A36 steel construction
- Manways
- Interior & exterior ladders
- Stilling wells
- Interior ANSI/NSF protective coatings
- Exterior rust inhibitors
- 150 PSI flanges
- Anti-vortex plate
-
Split float access panels
- Fill, suction, vent and drain
The BreakTank shall be divided with a partition with one
compartment for Fire Protection Water and the other for Potable
Water (Only Where Domestic Storage is Utilized). The partition
shall be of the double wall type extending to the top of the tank,
each wall of the partition shall be sealed with a continuous weld
between the wall and four sides of the tank. There shall be an air
space between the walls of the partition of not less than four (4)
inches for tanks with a height of ten (10) feet or less. For tanks
over ten (10) feet in height, the space between the walls of the
partition shall be not less than six (6) inches. A nonthreaded
opening shall be provided at the bottom of the partition to give
visual evidence of loss of integrity of the wall of the partition. The
air space between the partition walls shall be given a one (1) psi
air test with all welds soaped to assure no leaks in the partition
chamber. The tank fabricator shall furnish a notarized certificate of compliance with this test. A metal nameplate indicating the name
of manufacturer, date of manufacture and serial number of the
tank shall be permanently affixed to the tank. The manufacturer of
the tank shall have no less than five (5) years of experience
building 3,500 gallon or larger potable water tanks. No
subcontracting of tank will be permitted. A list of installations of
such tanks shall be furnished as required by the engineer. The
tanks shall be constructed entirely of new materials to assure
against the possibility of contamination from previous usage.
Other Models
Dolor Sit Amet
A
Additional Resources
File Preview ⬎
Related Products
Domestic Water Storage Tank •
Read more